A premises wiring system whose power is derived from a source of electric energy or equipment other than a service.
Switched neutral manual transfer switch.
This is known as a switched neutral system and the neutral switching can be open or overlapping closed.
If you cannot lift the bond disconnect the ground wire to the transfer switch at the generator or don t run a ground wire at all.
With a switched neutral the generator set can be wired as a separately derived system to the load and normal power supply.
Note that neither neutral nor ground are switched in the transfer switch.
For the generator to be considered a separately derived system the supply to the transfer switch must include a grounded neutral conductor and the transfer switch must switch the grounded neutral conductor example a 4 pole transfer switch for a 3 phase 4 wire system.
However a 3 pole transfer switch with overlapping neutral contacts has several drawbacks.
Also the neutral is designed to be switched simultaneously with the switching of the load carrying phases.
According to the 2011 national electrical code nec a separately derived power system is.
Three pole transfer switches with overlapping neutral contacts.
The generac 6297 30 amp switch neutral kit for manual transfer switches is designed to enable manual transfer switches up to 30 amp to isolate the utility and generator neutrals.
One disadvantage is the design and construction of the neutral pole and contacts.
If there is no grounded neutral conductor run to the transfer switch or if the transfer switch does not switch the grounded neutral conductor then the generator is not a separately derived system.
This type of transfer switch offers many advantages including the following.
The x series is perfect for use with generators having gfci protected outlets bonded neutral generators and installations requiring a separately derived system.
How to install a manual transfer switch for backup system in 16 steps.
A manual transfer switch is installed next to the main service panel to override the normal electrical service with power from a backup generator during a power outage.
It operates with little or no arcing which minimizes the risk of erosion or degradation of the neutral contact.
The switched neutral kit can upgrade most manual transfer switches from non switched neutral to switched neutral as required b y certain municipalities electrical inspectors and generators.
In this configuration the neutral is not solidly connected through the transfer switch but switched.
This switched neutral kit can be used in single phase manual transfer switches up to 30 amps 125 250v.
The new reliance panel link x series is a double pole manual transfer switch with an exclusive third pole for the neutral that switches sequentially.